Application Guide - NP900 Series
224 (504
)
A996A
Table 3.3.1.1-149. Output signals of the MST function
Name
Range
Step
Default
Description
Motor stopped
0=Not active
1=Active
1
0
Signal is active when the MST function
detects current below “No load current”.
This signal presents situation when the
motor is not running.
Motor starting
0=Not active
1=Active
1
0
Motor starting signal is active when motor
start up is detected. In DOL mode it is
active when measured current is exceeding
“Start detect current” from “Motor stopped”
situation until current decreases below
“Max overloading current”.
Motor running
0=Not active
1=Active
1
0
Motor running signal is active when
measured current is over the set “No load
current” after the “Motor starting” situation
is passed first. Motor running signal is
released when the measured current is
below “No load current” setting.
Motor stalled
0=Not active
1=Active
1
0
Motor stalled signal is active if the
measured current exceeds “Max overload
current” setting from the “Motor running”
situation.
Missing phase
0=Not active
1=Active
1
0
Missing phase signal is activated if one of
the phases measured current is below “No
load current” setting and two phases
measured current is over “Min. locked rotor
current” setting. This signal can be used for
quick halting the start up of the motor if one
phase is lost and the motor cannot start.
Load Normal
0=Not active
1=Active
1
0
Load normal signal is active when
measured current is over the set “No load
current” and under motor nominal current
including ambient and service factor
corrections.
Overloading
0=Not active
1=Active
1
0
Overloading signal is active if the measured
current exceeds the motor nominal current
including ambient and service factor
corrections but not over the set “Max
overload current” setting.
High overcurrent
0=Not active
1=Active
1
0
High overcurrent signal is active when the
measured current is over the set “Max
locked rotor current” and presents situation
which is impossible for the motor to cause
even starting or stalled. If this signal
activates it indicates short circuit fault and
should be used for halting start-up or
stalled situations immediately.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...