X20 system modules • Analog input modules • X20AP31x1
354
X20 system User's Manual 3.10
4.3.14.10.17 ADC RMS comparison checksum 3
4.3.14.10.17.1 Voltage RMS gain phase A/B/C
Name:
UGainA_W
UGainB_W
UGainC_W
Data type
Value
Information
UINT
0 to 65,535
Voltage RMS gain, phase-based
The resulting gain is calculated using the following formula:
Value
new
= Value
old
* correction factor, determined when U = U
n
4.3.14.10.17.2 Current RMS gain phase A/B/C/N
Name:
IGainA_W
IGainB_W
IGainC_W
IGainN_W
Data type
Value
Information
UINT
0 to 65,535
Current RMS gain, phase-based
The resulting gain is calculated using the following formula:
Value
new
= Value
old
* correction factor, determined when I = I
n
4.3.14.10.17.3 Voltage RMS offset phase A/B/C
Name:
UoffsetA_W
UoffsetB_W
UoffsetC_W
Corresponds to the negated value of the corresponding RMS register when U = 0.
Data type
Value
Information
INT
-32,767 to 32,767
RMS voltage offset, phase-based
4.3.14.10.17.4 Current RMS offset phase A/B/C/N
Name:
IoffsetA_W
IoffsetB_W
IoffsetC_W
IoffsetN_W
Corresponds to the negated value of the corresponding RMS register when I = 0.
Data type
Value
Information
INT
-32,767 to 32,767
RMS current offset, phase-based