X20 system modules • Expandable bus controllers • X20BC8083
1714
X20 system User's Manual 3.10
4.19.3.3 Technical data
Product ID
X20BC8083
Short description
Bus controller
POWERLINK (V1/V2) controlled node with up to two slots for hub expansion modules
General information
B&R ID code
0x2673
Status indicators
Module status, bus function
Diagnostics
Module status
Yes, with status LED and software status
Bus function
Yes, with status LED and software status
Power consumption
Bus
2.0 W
Additional power dissipation caused by the actua-
tors (resistive) [W]
-
Electrical isolation
Fieldbus - X2X Link
Yes
Fieldbus - I/O
Yes
Certification
CE
Yes
cULus
Yes
cCSAus HazLoc Class 1 Division 2
Yes
ATEX Zone 2
Yes
KC
Yes
GL
Yes
GOST-R
Yes
Interfaces
Fieldbus
POWERLINK (V1/V2) controlled node
Design
2x shielded RJ45 port (hub)
Cable length
Max. 100 m between two stations (segment length)
Transfer rate
100 Mbit/s
Transmission
Physical interfaces
100 BASE-TX
Half-duplex
Yes
Full-duplex
No
Autonegotiation
Yes
Auto-MDI / MDIX
Yes
Min. cycle time
1)
Fieldbus
200 μs
X2X Link
200 μs
Synchronization between bus systems possible
Yes
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at altitudes above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
Protection in accordance with EN 60529
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
-
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Note
Order 1x X20TB12 terminal block separately
Order 1x X20PS9400 or X20PS9402 power supply module separately
Order 1x X20BB8x bus base separately
Spacing
2)
X20BB80
37.5
+0.2
mm
X20BB81
62.5
+.02
mm
X20BB82
87.5
+0.2
mm
Table 502: X20BC8083 - Technical data
1)
The minimum cycle time defines how far the bus cycle can be reduced without communication errors occurring.
2)
Spacing is based on the width of the X20BB8x bus base. Up to two X20HB2880 hub expansion modules and one X20PS9400 or X20PS9402 supply module
are also always required for the bus controller.