X20 system modules • Digital output modules • X20DO2649
1106
X20 system User's Manual 3.10
4.15.7 X20DO2649
4.15.7.1 General information
The module has 2 relay outputs.
•
2 digital outputs
•
Relay module for 230 VAC / 30 VDC
•
2 change over contacts
•
Single-channel isolated outputs
Danger!
Risk of electric shock!
The terminal block must only be allowed to conduct voltage when it is inserted. It must not under any
circumstances be removed or inserted when voltage is applied or have voltage applied to it when it
is removed.
4.15.7.2 Order data
Model number
Short description
Figure
Digital output modules
X20DO2649
X20 digital output module, 2 relays, changeover contacts, 230
VAC / 5 A, 24 VDC / 5 A
Required accessories
Bus modules
X20BM11
Bus module, 24 VDC keyed, internal I/O supply continuous
Terminal blocks
X20TB12
X20 terminal block, 12-pin, 24 VDC keyed
Table 349: X20DO2649 - Order data
4.15.7.3 Technical data
Product ID
X20DO2649
Brief description
I/O module
2 digital outputs 30 VDC / 230 VAC, outputs are single-channel isolated
General information
B&R ID code
0x20DA
Status indicators
I/O function per channel, operating state, module status
Diagnostics
Module run/error
Yes, using status LED and software
Outputs
Yes, using status LED
Power consumption
Bus
0.45 W
Internal I/O
-
Additional power dissipation caused by the actua-
tors (resistive) [W]
1)
+2.5
Electrical isolation
Channel - Bus
Yes
Channel - Channel
Yes
Certification
CE
Yes
cULus
Yes
cCSAus HazLoc Class 1 Division 2
Yes
ATEX Zone 2
Yes
KC
Yes
GL
Yes
GOST-R
Yes
Digital outputs
Design
Relay / Changeover contact
Channels are single-channel isolated
Table 350: X20DO2649 - Technical data