X20 system modules • Analog input modules • X20AI2438
194
X20 system User's Manual 3.10
4.3.7.3 Technical data
Product ID
X20AI2438
Short description
I/O module
2 analog inputs, 4 to 20 mA or 0 to 25 mA
General information
B&R ID code
0xB3A9
Status indicators
I/O function per channel, operating state, module status, sensor supply per channel, HART
Diagnostics
Module run/error
Yes, using status LED and software status
Inputs
Yes, using status LED and software status
Sensor supply
Yes, using status LED and software status
HART link
Yes, using status LED and software status
HART error
Yes, using status LED and software status
Power consumption
Bus
0.05 W
Internal I/O
1.15 W
1)
External I/O
1.5 W
2)
Additional power dissipation caused by the actua-
tors (resistive) [W]
-
Electrical isolation
Channel - Bus
Yes
Channel - Channel
Yes
Certification
CE
Yes
cULus
Yes
ATEX Zone 2
Yes
KC
Yes
GOST-R
Yes
Analog inputs
Input
4 to 20 mA or 0 to 25 mA (can be configured via software)
Input type
Differential input
Digital converter resolution
15-bit
Data output rate
With HART
4.7 to 10 scans per second, can be set using software
Analog
4.7 to 100 scans per second, can be set using software
Output format
INT
Output format
4 to 20 mA
INT 0x0000 - 0x7FFF / 1 LSB = 0x0001 = 488.281 nA
0 to 25 mA
INT 0x0000 - 0x7FFF / 1 LSB = 0x0001 = 762.939 nA
0 to 25000 µA
INT 0x0000 - 0x61A8 / 1 LSB = 0x0001 = 1000 nA
Load
<300 Ω
Input protection
Up to 30 VDC, reverse polarity protection (max. 0.1 A)
Open line detection
Yes, via software
Permitted input signal
0 to 25 mA
Output of the digital value during overload
Configurable
Conversion procedure
Sigma Delta
Max. error at 25°C
Gain
0 to 25 mA
<0.046%
3)
4 to 20 mA
<0.046%
3)
Offset
0 to 25 mA
<0.004%
4)
4 to 20 mA
<0.013%
4)
Common-mode rejection
DC
80 dB
50 Hz
Depends on the sampling rate: e.g. >130 dB for 50 scans per second
Common-mode range
0 to 7 V
Non-linearity
<0.003%
4)
Input filter
Hardware
1st-order low pass / cut-off frequency 100 Hz
Software
Sinc
4
filter
Maximum gain drift
0 to 25 mA
0.003 %/°C
3)
4 to 20 mA
0.003 %/°C
3)
Maximum offset drift
0 to 25 mA
0.0002 %/°C
4)
4 to 20 mA
0.0007 %/°C
4)
Test voltage between
Channel and channel
1500 VAC
Channel and bus
1500 VAC
To ground
1500 VAC
Sensor supply
Nominal voltage
25 V ±2 %
Nominal output current
Max. 30 mA
Table 42: X20AI2438 - Technical data