X20 system modules • Expandable bus controllers • X20BC80G3
X20 system User's Manual 3.10
1733
4.19.5.2 Order data
Model number
Short description
Figure
Expandable bus controllers
X20BC80G3
X20 bus controller, EtherCAT interface, supports expansion with
X20 EtherCAT junction modules, 2x RJ45 connection, order bus
base, supply module and terminal separately!
Required accessories
System modules for bus controllers
X20PS9400
X20 supply module, for bus controller and internal I/O supply,
X2X Link supply
X20PS9402
X20 supply module, for bus controller and internal I/O supply,
X2X Link supply, supply not electrically isolated
System modules for expandable bus controllers
X20BB81
X20 bus base, for X20 base module (BC, HB, etc.) and X20
power supply module, with one expansion slot for an X20 add-
on module (IF, HB, etc.), X20 locking plates (left and right)
X20AC0SL1/X20AC0SR1 included
System modules for the X20 hub system
X20HB28G0
X20 EtherCAT junction module, integrated 2-port EtherCAT
junction, 2x RJ45
Terminal blocks
X20TB12
X20 terminal block, 12-pin, 24 VDC keyed
Table 512: X20BC80G3 - Order data
4.19.5.3 Technical data
Product ID
X20BC80G3
Short description
Bus controller
EtherCAT bus controller with one slot for a junction module
General information
B&R ID code
0xAEC2
Status indicators
Module status, bus function
Diagnostics
Module status
Yes, with status LED and software status
Bus function
Yes, with status LED and software status
Power consumption
Bus
1.79 W
Additional power dissipation caused by the actua-
tors (resistive) [W]
-
Electrical isolation
Fieldbus - X2X Link
Yes
Fieldbus - I/O
Yes
Certification
CE
Yes
cULus
Yes
cCSAus HazLoc Class 1 Division 2
Yes
ATEX Zone 2
Yes
KC
Yes
GOST-R
Yes
Interfaces
Fieldbus
EtherCAT slave
Design
2x shielded RJ45 port
Cable length
Max. 100 m between two stations (segment length)
Transfer rate
100 Mbit/s
Transmission
Physical interfaces
100 BASE-TX
Half-duplex
Yes
Full-duplex
Yes
Autonegotiation
Yes
Auto-MDI / MDIX
Yes
Min. cycle time
1)
Fieldbus
200 μs
X2X Link
200 μs
Synchronization between bus systems possible
Yes
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at altitudes above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
Protection in accordance with EN 60529
IP20
Table 513: X20BC80G3 - Technical data