X20 system modules • Analog input modules • X20AP31x1
352
X20 system User's Manual 3.10
4.3.14.10.14 ADC measurement configuration checksum 0
4.3.14.10.14.1 High word for power line constants
Name:
PLconstH
Data type
Value
UINT
0 to 65,535
Basis value of power line constant = 0x4A817C80 = 1,250,000,000 corresponding to 360 CF pulses per kWh
or 0.1 CF pulse per kWs. The result of setting the resolution in the energy registers to a decimal (see register
"MeteringMode" <Bit 9>) is 1 kWs per digit. Power line constant / 10 results in a 10x resolution.
4.3.14.10.14.2 Low word for power line constants
Name:
PLconstL
Data type
Value
UINT
0 to 65,535
Basis value of power line constant = 0x4A817C80 = 1,250,000,000 corresponding to 360 CF pulses per kWh
or 0.1 CF pulse per kWs. The result of setting the resolution in the energy registers to a decimal (see register
"MeteringMode" <Bit 9>) is 1 kWs per digit. Power line constant / 10 results in a 10x resolution.
4.3.14.10.14.3 Analog ADC measurement setting 1
Name:
MeteringMode
Data type
Value
UINT
See bit structure
Bit structure:
Bit
Name
Value
Information
0
Not enabled
0
Enables phase C for adding the power and energy values to-
gether
1
Approved
1)
0
Not enabled
1
Enables phase B for adding the power and energy values to-
gether
1
Approved
1)
0
Not enabled
2
Enables phase A for adding the power and energy values to-
gether
1
Approved
1)
0
Arithmetic sum
1)
3
Calculation method for adding active power and active energy
1
Absolute sum
0
Arithmetic sum
1)
4
Calculation method for adding reactive power and reactive en-
ergy
1
Absolute sum
5
Reserved
0
0
Arithmetic sum
1)
6
Selects apparent energy for CF2 source
1
Vector sum
0
Apparent energy
7
CF2 source
1
Reactive energy
1)
0
3P4W
1)
8
Measuring configuration
1
3P3W
0
0.1 CF
1)
9
Resolution of energy register
1
0.01 CF
0
Disabled
10
Integrator for didt current transformer
1
Enabled
0
Enabled
11
High-pass filter
1
Disabled
0
50 Hz
1)
12
Basis frequency
1
60 Hz
0
I1 to Phase A and I3 to Phase C
1)
13
Phase assignment
1
I1 to Phase C and I3 to Phase A
14 - 15
Reserved
0
1)
Standard in the bus controller function model
Comments regarding measurement configurations:
Measuring configuration
Note
3P4W
Monitors the phasing of voltages and currents: Phase A before phase B before phase C
Measuring configuration: Phase A and phase C, N connection bridges to phase B or open
Measurement: e.g. the 2 phases A and C and the 2 corresponding currents are measured, phase B disabled
3P3W
Monitors the phasing of voltages and currents: Phase difference between A and C >180°