X20 system modules • X20 electronics module communication • X20CS1011
1462
X20 system User's Manual 3.10
4.18.2.3 Technical data
Product ID
X20CS1011
Short description
Communication module
1 SmartWire master for controlling up to 16 slaves
General information
B&R ID code
0xA38D
Status indicators
SmartWire bus function, external supply voltage, operating state, module status
Diagnostics
Module run/error
Yes, using status LED and software
SmartWire operating state
Yes, using status LED and software
U Aux
Yes, using status LED
Power output
Internal I/O
6.8 W for supplying external slaves (equal to 16 slaves each with 0.425 W)
Power consumption
Bus
0.01 W
Internal I/O
1.5 W
Additional power dissipation caused by the actua-
tors (resistive) [W]
-
Electrical isolation
SmartWire bus - X2X Link
Yes
SmartWire supply (17 VDC) - I/O supply
No
Certification
CE
Yes
cULus
Yes
cCSAus HazLoc Class 1 Division 2
Yes
ATEX Zone 2
Yes
KC
Yes
GOST-R
Yes
Interfaces
Interface
Type
SmartWire (LIN bus)
Design
Connection made using 12-pin X20TB12 terminal block
Transfer rate
19200 bit/s
SmartWire
Data format
1 start bit, 8 data bits, no parity bit, 1 stop bit
Max. distance
4 m
Configuration button
Internal
Integrated in the module on the bottom of the housing.
External
Connection via 12-pin terminal block
N.O. contact, not electrically isolated (use potential-free contact)
SWIRE terminal 1 (24 VDC)
Voltage drop for reverse polarity protection at
3 A
Max. 0.1 VDC
Voltage range
Voltage and supply
Current load
Max. 3 A
Short circuit protection
No, only with external fuse
Monitoring
20 VDC < 24 VDC Aux < 29.4 VDC (via firmware)
SWIRE terminal 2
Daisy chain signal
5 VDC, CMOS level
SWIRE terminal 5 (bus level)
Dominant
<2 VDC
Recessive
>14.85 VDC
SWIRE terminal 6 (17 VDC)
Voltage range
Typ. 16.6 VDC (16.3 VDC to 16.8 VDC)
Summation current
Max. 400 mA for 16 SmartWire slaves
Short circuit protection
Yes
Monitoring
14.2 VDC < 17 VDC Aux < 17.9 VDC (via firmware)
U-Aux (24 VDC aux supply)
Connection
Externally via 12-pin terminal block
1)
Input voltage
24 VDC -15% / +20%
Fuse
Recommended line fuse: 3 A, slow-blow
Summation current
Max. 3 A for 16 SmartWire slaves
Reverse polarity protection
Yes
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at elevations above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
EN 60529 protection
IP20
Table 452: X20CS1011 - Technical data