X20 system modules • Digital output modules • X20DO6325
X20 system User's Manual 3.10
1219
4.15.19.11.5.5 Cumulative status
Name:
StatusInput04
DigitalStatusSum01 to DigitalStatusSum06
PowerSupply01
Every error found in the other status registers is also shown in this register. This provides an easy way to check
whether any errors have occurred.
If the I/O supply fails, Bit 7 is set and all status bits in the other status registers are reset to 0.
Function model 0 - Standard only:
The "packed outputs" setting in the AS I/O configuration is used to determine whether all of this registers' bits should
be set up individually as data points ("DigitalStatusSum01 through DigitalStatusSum06","PowerSupply01") in the
AS I/O mapping or whether this register should be displayed as an individual USINT data point ("StatusInput04").
Data type
Value
Information
0 to 255
Packed outputs = on
USINT
See bit structure
Packed outputs = off or function model <> 0 - Standard
Bit structure:
Bit
Name
Value
Information
0
No error
0
DigitalStatusSum01
1
Channel 1: Error occurred
...
...
0
No error
5
DigitalStatusSum06
1
Channel 6: Error occurred
6
Reserved
0
0
No error
7
PowerSupply01
1
Pending supply voltage error