Product ID
X20DO6529
Nominal voltage
30 VDC / 115 VAC
Switching voltage
Max. 110 VDC / 125 VAC
Rated frequency
DC / 45 to 63 Hz
Nominal output current
1.0 A at 30 VDC / 0.5 A at 115 VAC
Total nominal current
6.0 A at 30 VDC / 3.0 A at 115 VAC
Actuator supply
External
Starting current
Max. 2 A (per channel)
Contact resistance
75 mΩ at 6 VDC / 1A
Switching delay
0 -> 1
≤4 ms
1 -> 0
≤4 ms
Isolation voltage
Contact - Contact
Tested at 1000 VAC
Contact - Coil
Tested at 1500 VAC
Service life
Electrical
2)
Min. 100 x 10³ ops.
Mechanical
Min. 50 x 10
6
ops. (3 Hz)
Switching capacity
Minimum
0.01 mA / 10 mV DC
Maximum
30 W / 62.5 VA
Protective circuit
Internal
None
External
AC
RC combination or VDR
DC
Inverse diode, RC combination or VDR
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at elevations above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
EN 60529 protection
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
See section "Derating"
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Note
Order 1x X20TB12 terminal block separately
Order 1x X20BM11 bus module separately
Spacing
12.5
+0.2
mm
Table 390: X20DO6529 - Technical data
1)
Number of outputs x Contact resistance x Nominal output current
2
(A calculation example can be found on the B&R website in the download area for the
module.)
2)
With a resistive load. See also section "Electrical service life"