Coated modules • Bus controllers • X20cBC0083
X20 system User's Manual 3.10
2517
5.5.2.3 Technical data
Product ID
X20cBC0083
Brief description
Bus controllers
POWERLINK (V1/V2) controlled node
General information
B&R ID code
0xE216
Status indicators
Module status, bus function
Diagnostics
Module status
Yes, using status LED and software
Bus function
Yes, using status LED and software
Power consumption
Bus
2 W
Additional power dissipation caused by the actua-
tors (resistive) [W]
-
Electrical isolation
Fieldbus - X2X Link
Yes
Fieldbus - I/O
Yes
Certification
CE
Yes
cULus
Yes
ATEX Zone 2
Yes
GL
Yes
GOST-R
Yes
Interfaces
Fieldbus
POWERLINK (V1/V2) controlled node
Design
2x shielded RJ45 port (hub)
Cable length
Max. 100 m between two stations (segment length)
Transfer rate
100 Mbit/s
Transmission
Physical interfaces
100 BASE-TX
Half-duplex
Yes
Full-duplex
No
Autonegotiation
Yes
Auto-MDI / MDIX
Yes
Min. cycle time
1)
Fieldbus
200 μs
X2X Link
200 μs
Synchronization between bus systems possible
Yes
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at elevations above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
EN 60529 protection
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
-
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
Up to 100%, condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Note
Order 1x X20TB12 terminal block separately
Order 1x X20cPS9400 power supply module separately
Order 1x X20cBB80 bus base separately
Spacing
2)
37.5
+0.2
mm
Table 923: X20cBC0083 - Technical data
1)
The minimum cycle time defines how far the bus cycle can be reduced without communication errors occurring.
2)
Spacing is based on the width of the X20BB80 bus base. An X20PS9400 or X20PS9402 power supply module is always required for the bus controller.