X20 system modules • X20 interface module communication • X20IF1091
X20 system User's Manual 3.10
1831
4.23.17.3 Technical data
Product ID
X20IF1091
Short description
Communication module
1x X2X Link master
General information
B&R ID code
0x1F24
Status indicators
Module status, data transfer
Diagnostics
Module status
Yes, using status LED
Data transfer
Yes, using status LED
Power consumption
0.97 W
Additional power dissipation caused by the actua-
tors (resistive) [W]
-
Electrical isolation
PLC - IF1
Yes
Certification
CE
Yes
cULus
Yes
cCSAus HazLoc Class 1 Division 2
Yes
ATEX Zone 2
Yes
KC
Yes
GOST-R
Yes
Interfaces
IF1 interface
Fieldbus
X2X Link master
Design
4-pin male multipoint connector
Number of stations
Max. 253
Bus terminating resistor
Internal
Internal bus supply
No
Network topology
Line
Distance between 2 stations
Max. 100 m
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at elevations above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
EN 60529 protection
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
-
Storage
-40 to 85°C
Transport
-40 to 85°C
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Note
Order 1x TB704 terminal block separately
Slot
In X20 CPU
Table 621: X20IF1091 - Technical data