4.15.13.3 Technical data
Product ID
X20DO4613
Short description
I/O module
4 digital outputs for controlling external power triacs or non-parallel thyristors
General information
B&R ID code
0xAD05
Status indicators
I/O function per channel, operating state, module status
Diagnostics
Module run/error
Yes, using status LED and software
Outputs
Yes, using status LED
Power consumption
Bus
0.8 W
Internal I/O
-
External I/O
-
Additional power dissipation caused by the actua-
tors (resistive) [W]
1)
+1 W
Electrical isolation
Channel - Bus
Yes
Channel - Channel
Yes
Certification
CE
Yes
cULus
Yes
ATEX Zone 2
Yes
KC
Yes
GOST-R
Yes
Digital outputs
Design
Opto-triac
Wiring
N.O. contact
Nominal voltage
48 to 240 VAC
Rated frequency
47 to 63 Hz
Rated current at 25°C
Nominal output current
80 mA
Total nominal current
320 mA
Current over entire temperature range
Output current
50 mA
Summation current
200 mA
Connection type
2-wire connections
Zero-crossing detection
Yes
Holding current
Max. 3.5mA
Leakage current
Max. 1.5 mA (per channel)
Residual voltage (on-state voltage)
Max. 3V
Phase-angle control
Range
5 to 95%
Resolution
1%
Accuracy (60 to 240 VAC)
<100 μs
Voltage monitoring L - N
No
Recommended cabling
Twisted pair cabling to the terminal pairs
Cable length
Max. 10 m
Overvoltage protection between L and N
Yes
Isolation voltage
Channel - Bus
Tested at 2300 VAC
Channel - Channel
Tested at 2300 VAC
Protective circuit
External
General protection
Internal
Snubber circuit (RC element) and varistor
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at elevations above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
EN 60529 protection
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
-25 to 60°C
Vertical installation
-25 to 50°C
Derating
-
Storage
-40 to 85°C
Transport
-40 to 85°C
Table 370: X20DO4613 - Technical data