X20 system modules • Other functions • X20CM4810
X20 system User's Manual 3.10
2175
4.26.2.5.7 Module registers - Characteristic values (acyclic)
The following applies to all characteristic value module registers:
•
These registers are only available in Function model 2 - Slow master and Function model 254 - Bus con-
troller.
•
All calculated characteristic values can be locked using RequestDataLock01, which allows all registers to
be read in a consistent manner.
4.26.2.5.7.1 CrestFactorRaw01-04
Asynchronous register for reading the characteristic value "CrestFactorRaw" of the respective channel.
Since division by the RMS value takes place in the module ("RmsRaw"), there may be an overflow if the RMS value
is very small. To prevent this, the module has an internal lower limit of 1 mg for the RMS value.
Format
Resolution and unit
Value on overflow
24-bit unsigned
0.001
16777215
Characteristic value after preparation by Automation Runtime in Function model 0 - Standard
Format
Unit
REAL
1
4.26.2.5.7.2 FrequencyBand01-32
Asynchronous
register
to
read
the
respective
frequency
band.
See
section
4.26.2.2.9 "Frequency bands" on page 2074.
If the frequency band parameter is set to a velocity signal, then this value is only calculated if the EnableVelocity-
Calculation bit (configured in the "SensorConfig01" register) for the respective channel is set; otherwise, 0 is output.
Format
Resolution and unit
Value on overflow
24-bit unsigned
0.001 g or 0.001 mm/s
depending on the configuration
16777215
24-bit unsigned
1/65536 g or 1/65536 mm/s
depending on the configuration
16777215
Parameter after preparation by Automation Runtime in Function model 0 - Standard
Format
Unit
REAL
mg or mm/s depending on the configuration
4.26.2.5.7.3 Iso10816_01-04
Asynchronous register for reading the characteristic value "ISO10816" of the respective channel.
Format
Resolution and unit
Value on overflow
24-bit unsigned
0.001 mm/s
16777215
Characteristic value after preparation by Automation Runtime in Function model 0 - Standard
Format
Unit
REAL
mm/s
4.26.2.5.7.4 KurtosisRaw01-04
Asynchronous register for reading the characteristic value "KurtosisRaw" of the respective channel.
Since division by the RMS value takes place in the module ("RmsRaw"), there may be an overflow if the RMS value
is very small. To prevent this, the module has an internal lower limit of 1 mg for the RMS value.
Format
Resolution and unit
Value on overflow
24-bit signed
0.001
8388607
Characteristic value after preparation by Automation Runtime in Function model 0 - Standard
Format
Unit
REAL
1