X20 system modules • Analog input modules • X20AP31x1
346
X20 system User's Manual 3.10
4.3.14.10.10.20 Reverse harmonics active energy on phase A/B/C
Name:
ANenergyAH
ANenergyBH
ANenergyCH
Harmonics of active energy in reverse direction of the phase.
Data type
Value
Information
UDINT
0 to 4,294,967,295
Resolution 0.1 or 0.01 CF, depending on the Power Line factor (e.g. kWs)
Comments:
•
The unit CF is derived from the Power Line factor (default: 3600 Imp/kWh), see register "MeteringMode"
•
The resolution can be switched between 0.1 and 0.01, see register "MeteringMode"
•
The register is updated automatically after being enabled, see register "ControlOutput" <Bit 1>
•
The register is cleared upon request, see register "ControlOutput"
•
The register is set upon request, see register "ControlOutput" <Bit 3>
4.3.14.10.10.21 Total active energy combined
Name:
AEnergyT
Total active energy in forward and backward direction.
Data type
Value
Information
DINT
-2,147,483,647 to 2,147,483,647
Resolution 0.1 or 0.01 CF, depending on the Power Line factor (e.g. kWs)
Internal calculation formula for the total active energy:
AEnergyT = (DINT)(APenergyT - ANenergyT) ... Calculation overflows must be handled in the application
Comments:
•
The unit CF is derived from the Power Line factor (default: 3600 Imp/kWh), see register "MeteringMode"
•
The resolution can be switched between 0.1 and 0.01, see register "MeteringMode"
•
The register is updated automatically after being enabled, see register "ControlOutput" <Bit 1>
•
The register is cleared upon request, see register "ControlOutput"
•
The register is set upon request, see register "ControlOutput" <Bit 3>
4.3.14.10.10.22 Total reactive energy combined
Name:
REnergyT
Total reactive energy in forward and backward direction.
Data type
Value
Information
DINT
-2,147,483,647 to 2,147,483,647
Resolution 0.1 or 0.01 CF, depending on the Power Line factor (e.g. kWs)
Internal calculation formula for the total reactive energy:
REnergyT = (DINT)(RPenergyT - RNenergyT) ... Calculation overflows must be handled in the application
Comments:
•
The unit CF is derived from the Power Line factor (default: 3600 Imp/kWh), see register "MeteringMode"
•
The resolution can be switched between 0.1 and 0.01, see register "MeteringMode"
•
The register is updated automatically after being enabled, see register "ControlOutput" <Bit 1>
•
The register is cleared upon request, see register "ControlOutput"
•
The register is set upon request, see register "ControlOutput" <Bit 3>