X20 system modules • Digital input modules • X20DI4375
X20 system User's Manual 3.10
981
4.13.8.13.3 Digital inputs
Unfiltered
The input state is collected with a fixed offset to the network cycle and transferred in the same cycle.
Filtered
The filtered status is collected with a fixed offset to the network cycle and transferred in the same cycle. Filtering
takes place asynchronously to the network in multiples of 200 µs with a network-related jitter of up to 50 µs.
4.13.8.13.3.1 Digital input filter
Name:
ConfigOutput02
This register can be used to specify the filter value for all digital inputs.
The filter value can be configured in steps of 100 μs. It makes sense to enter values in steps of 2, however, since
the input signals are sampled every 200 μs.
Data type
Value
Filters
0
No software filter
2
0.2 ms
...
...
USINT
250
25 ms - Higher values are limited to this value
4.13.8.13.3.2 Input status of digital inputs 1 to 4
Name:
DigitalInput or
DigitalInput01 to DigitalInput04
StateDigitalInput01 to StateDigitalInput04
The input status and status of digital inputs 1 to 4 are mapped in this register.
Function model 0 - Standard only:
The "packed inputs" setting in the AS I/O configuration is used to determine whether all of this register's bits
should be set up individually as data points in the AS I/O mapping ("DigitalInput01" through "DigitalInput04" and
"StateDigitalInput01" through "StateDigitalInput04") or whether this register should be displayed as an individual
USINT data point ("DigitalInput").
Data type
Value
Information
0 to 255
Packed inputs = on
USINT
See bit structure
Packed inputs = off or function model <> 0 - Standard
Bit structure:
Bit
Name
Value
Information
0
DigitalInput01
0 or 1
Input status - Digital input 1
...
...
3
DigitalInput04
0 or 1
Input status - Digital input 4
0
No error
4
StateDigitalInput01
1
Short-circuit, open line, sensor monitoring error or other channel
error
...
...
0
No error
7
StateDigitalInput04
1
Short-circuit, open line, sensor monitoring error or other channel
error