Coated modules • Analog input modules • X20cAI2438
2490
X20 system User's Manual 3.10
5.3.2.3 Technical data
Product ID
X20cAI2438
Short description
I/O module
2 analog inputs, 4 to 20 mA or 0 to 25 mA
General information
B&R ID code
0xE1EE
Status indicators
I/O function per channel, operating state, module status, sensor supply per channel, HART
Diagnostics
Module run/error
Yes, using status LED and software
Inputs
Yes, using status LED and software
Sensor supply
Yes, using status LED and software
HART link
Yes, using status LED and software
HART error
Yes, using status LED and software
Power consumption
Bus
0.05 W
Internal I/O
1.15 W
1)
External I/O
1.5 W
2)
Additional power dissipation caused by the actua-
tors (resistive) [W]
-
Electrical isolation
Channel - Bus
Yes
Channel - Channel
Yes
Certification
CE
Yes
cULus
Yes
ATEX Zone 2
3)
Yes
GL
Yes
GOST-R
Yes
Analog inputs
Input
4 to 20 mA or 0 to 25 mA (can be configured using software)
Input type
Differential input
Digital converter resolution
15-bit
Data output rate
With HART
4.7 to 10 scans per second, can be configured using software
Analog
4.7 to 100 scans per second, can be configured using software
Output format
INT
Output format
4 to 20 mA
INT 0x0000 - 0x7FFF / 1 LSB = 0x0001 = 488.281 nA
0 to 25 mA
INT 0x0000 - 0x7FFF / 1 LSB = 0x0001 = 762.939 nA
0 to 25,000 µA
INT 0x0000 - 0x61A8 / 1 LSB = 0x0001 = 1000 nA
Load
<300 Ω
Input protection
Up to 30 VDC, reverse polarity protection (max. 0.1 A)
Open line detection
Yes, using software
Permitted input signal
0 to 25 mA
Output of the digital value during overload
Configurable
Conversion procedure
Sigma Delta
Max. error at 25°C
Gain
0 to 25 mA
<0.046%
4)
4 to 20 mA
<0.046%
4)
Offset
0 to 25 mA
<0.004%
5)
4 to 20 mA
<0.013%
5)
Common-mode rejection
DC
80 dB
50 Hz
Depends on the sampling rate: e.g. >130 dB for 50 scans per second
Common-mode range
0 to 7 V
Nonlinearity
<0.003%
5)
Input filter
Hardware
1st-order low pass / cut-off frequency 100 Hz
Software
Sinc
4
filter
Max. gain drift
0 to 25 mA
0.003 %/°C
4)
4 to 20 mA
0.003 %/°C
4)
Max. offset drift
0 to 25 mA
0.0002 %/°C
5)
4 to 20 mA
0.0007 %/°C
5)
Test voltage between
Channel and channel
1000 VAC
Channel and bus
1000 VAC
To ground
1000 VAC
Sensor supply
Nominal voltage
25 V ±2%
Nominal output current
Max. 30 mA
Table 903: X20cAI2438 - Technical data