X20 system modules • Bus controllers • X20BC0053
522
X20 system User's Manual 3.10
Product ID
X20BC0053
Power consumption
Bus
1.5 W
Additional power dissipation caused by the actua-
tors (resistive) [W]
-
Electrical isolation
Fieldbus - X2X Link
No
Fieldbus - I/O
Yes
Certification
CE
Yes
cULus
Yes
cCSAus HazLoc Class 1 Division 2
Yes
ATEX Zone 2
Yes
KC
Yes
GOST-R
Yes
Interfaces
Fieldbus
DeviceNet adapter (slave)
Design
5-pin male multipoint connector
Max. distance
500 m
Transfer rate
Max. 500 kbit/s
Determination of transfer rate
Automatic transfer rate detection
Terminating resistor
Integrated in the module
Min. cycle time
1)
Fieldbus
No limitations
X2X Link
400 μs
Synchronization between bus systems possible
No
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at altitudes above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
Protection in accordance with EN 60529
IP20
Environmental conditions
Temperature
Operation
Horizontal installation
0 to 55°C
Vertical installation
0 to 50°C
Derating
-
Storage
-25 to 70°C
Transport
-25 to 70°C
Relative humidity
Operation
5 to 95%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Mechanical characteristics
Note
Order 1x TB2105 terminal block separately
Order 1x X20TB12 terminal block separately
Order 1x X20PS9400 or X20PS9402 power supply module separately
Order 1x X20BB80 bus base separately
Spacing
2)
37.5
+0.2
mm
Table 125: X20BC0053 - Technical data
1)
The minimum cycle time defines how far the bus cycle can be reduced without communication errors occurring.
2)
Spacing is based on the width of the X20BB80 bus base. In addition, an X20PS9400 or X20PS9402 supply module is always required for the bus controller.
4.5.4.4 LED status indicators
Figure
LED
Color
Status
Description
Off
Bus sense error:
If the "NET" LED is also "off", there is no 24 V DeviceNet voltage.
No transfer rate:
If the PS9400's "RUN" LED is active (PREOPERATIONAL or RUN mode), the
automatic transfer rate detection is still running or no transfer rate could be de-
tected.
On
RUN mode:
The 24 V DeviceNet voltage is OK and the module is operating under normal
conditions.
Green
Blinking
Standby mode:
Configuration is missing, incomplete, or incorrect.
Red
Blinking
Recoverable Fault mode:
MOD
1)
Green/red
Blinking
Module is performing a self test.
Table 126: LED status indicators