X20 system modules • Digital output modules • X20DO2633
X20 system User's Manual 3.10
1103
4.15.6.14.8 Status of the outputs
Name:
LowCurrentStatus1 through LowCurrentStatus2
ZeroCrossingInput
ZeroCrossingStatus
StatusInput01
The operating status of the outputs is mapped in this register.
In order to do determine the "LowCurrentStatus", the system checks if there is a neutral connection from the output
via the consumer shortly before each triac firing.
Function model 0 - Standard only:
The "packed outputs" setting in the AS I/O configuration is used to determine whether all of this registers' bits should
be set up individually as data points in the AS I/O mapping ("LowCurrentStatus1" through "ZeroCrossingStatus")
or whether this register should be displayed as an individual USINT data point ("StatusInput01").
Data type
Value
Information
0 to 255
Packed outputs = on
USINT
See bit structure
Packed outputs = off or function model <> 0 - Standard
Bit structure:
Bit
Name
Value
Information
0
Current flow on activated output 1
0
LowCurrentStatus1
1
No current flow on activated output 1
0
Current flow on activated output 2
1
LowCurrentStatus2
1
No current flow on activated output 2
2 - 3
Reserved
-
0
Zero cross signal during the negative half-wave
4
ZeroCrossingInput
1
Zero cross signal during the positive half-wave
5 - 6
Reserved
-
0
Zero cross signal OK
7
ZeroCrossingStatus
1
Zero cross signal has dropped out