INSTRUCTION MANUAL
TOTALIZED PULSE INPUT MODULE, 8 points
(DeviceNet)
MODEL
R7D-PA8
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■
PACKAGE INCLUDES:
Totalized pulse input module .............................................(1)
■
MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■
INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
■
EDS FILE
EDS files are downloadable at M-System’s web site: http://
www.m-system.co.jp
POINTS OF CAUTION
■
CONFORMITY WITH EU DIRECTIVES
• The equipment must be mounted inside the instrument
panel of a metal enclosure.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.
■
GENERAL PRECAUTIONS
• Before you remove the unit or mount it, turn off the power
supply and input signal for safety.
• DO NOT set the switches on the module while the power
is supplied. The switches are used only for maintenance
without the power.
■
ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■
WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
COMPONENT IDENTIFICATION
5
4
3
2 1 0 9
8
7
6
5
4
3
2 1 0 9
8
7
6
5
4
3
2 1 0 9
8
7
6
MS
X10
X1
NODE ADD.
B.RATE
CNFG.
1
2
3
4
5
6
7
8
0
1
2
3
4
5
6
7
10 11 12 13
2
3
4
1
15 16 17 18
7
8
9
6
14
5
NS
2 3 4
1
5
(A) Status Indicator LED
(B) Node Address Setting Rotary SW
(C) Baud Rate Setting Rotary SW
(D) Operating Mode Setting DIP SW (SW1)
(E) PC Configurator Jack
(F) Input Status Indicator LED
(G) DeviceNet, Power Supply Terminals
(H) Input Terminals
(A)
(B)
(C)
(D)
(E)
(F)
(G)
(H)
■
STATUS INDICATOR LED
ID
STATE
FUNCTION
MS
Green
Operating in a normal condition
Blinking Green Standby (needs commissioning)
Red
Critical failure
Blinking Red
Minor failure
OFF
No power supplied
NS
Green
Link on-line and connections in the
established state
Blinking Green Link on-line but no connections in
the established state
Red
Critical link failure
Blinking Red
Minor link failure
OFF
No power supplied
■
PULSE INPUT STATUS INDICATOR LED
LED indicators showing input signal status.
ON : LED ON
OFF : LED OFF
■
NODE ADDRESS
Node Address is selected between 1 and 63 in decimal. The
left switch determines the tenth place digit, while the right
switch does the ones place digit of the address.
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
Node Address Setting (x1)
Factory setting : 00
Node Address Setting (x10)