The Reliable Automatic Sprinkler Co., Inc.,

 

103 Fairview Park Drive, Elmsford, New York 10523

Model F156 EC Series
Standard Response
Extended Coverage  Spray

Bulletin 

027 Rev

.

 C

Bulletin 027 

Rev.

 C

Model F156 EC

Extended Coverage  Sprinkler

• Pendent

Model F156 EC Recessed

Extended Coverage Sprinkler

•  Recessed Pendent F1/F2/FP

Approval Organizations

1. Listed by Underwriters Laboratories, Inc. and 

    

Certified for Canada (cULus)

UL Listing Category

Sprinklers, Automatic & Open (VNIV)

Product Description

The F156 Extended Coverage Glass Bulb Sprinkler com-

bines the durability of a standard sprinkler with the attrac-
tive low profile of a decorative sprinkler. Whether installed 
on exposed piping or in an office ceiling, it is functional 
and attractive.

Beautifully versatile is the description for the Reliable 

Model F156 Recessed Extended Coverage glass bulb 
sprinkler. Recessing the sprinkler enhances its already 
low profile decorative appearance, and facilitates a rapid 
and perfect installation.

Model F156 Recessed Extended Coverage escutcheon 

is highly adjustable.  The two piece construction makes 
field installation a very easy and rapid task.  This also al-
lows ceiling panels to later be removed without shutting 
down the fire protection system, thus facilitating mainte-
nance of above ceiling services.

The Model F156 Extended Coverage Sprinkler utilizes 

a frangible glass bulb. The glass bulb consists of an ac-
curately controlled amount of special fluid hermetically 
sealed inside of a precisely manufactured glass capsule. 
This glass bulb is specially constructed to provide fast 
thermal response.

At normal temperatures, the glass bulb contains the fluid 

in both the liquid phase and in the vapor phase. The vapor 
phase can be seen as a small bubble. As heat is applied, 
the liquid expands forcing the bubble smaller and smaller 
as the liquid pressure increases. Continued heating forces 
the liquid to push out against the bulb, causing the glass 
to shatter, opening the waterway and allowing the deflec-
tor to distribute the discharging water.

The F156 Extended Coverage Sprinkler temperature rat-

ing is identified by the color of the glass bulb capsule as 
well as frame color where applicable.

Recessed Extended Coverage

Pendent F1/F2

Extended Coverage

 Pendent

Recessed Extended Coverage

Pendent FP

Содержание F156 EC Series

Страница 1: ...djustable The two piece construction makes field installation a very easy and rapid task This also al lows ceiling panels to later be removed without shutting down the fire protection system thus facilitating mainte nance of above ceiling services The Model F156 Extended Coverage Sprinkler utilizes a frangible glass bulb The glass bulb consists of an ac curately controlled amount of special fluid ...

Страница 2: ...Identification Number SIN US Metric F C 15mm NPT R 5 6 80 2 25 57mm 135 155 57 68 RA2745 Model F156 Recessed Extended Coverage Pendent Sprinkler Deflector EC Pendent Installation Wrench Model GFR2 Sprinkler Wrench Approval Type Extended Coverage Light Hazard Occupancy Installation Data 1 Nominal Orifice Thread Size Nominal K Factor Sprinkler Height Temperature Rating Sprinkler Identification Numbe...

Страница 3: ...spare sprinklers should be maintained to allow quick replace ment of damaged or operated sprinklers Prior to instal lation sprinklers should be maintained in the original car tons and packaging until used to minimize the potential for damage to sprinklers that would cause improper opera tion or non operation Escutcheon Data Escutcheon Model Adjustment A Dimension Face of Fitting to Ceiling or Wall...

Страница 4: ...throughout the United States Canada and foreign countries Automatic sprinklers Flush automatic sprinklers Recessed automatic sprinklers Concealed automatic sprinklers Adjustable automatic sprinklers Dry automatic sprinklers Intermediate level sprinklers Open sprinklers Spray nozzles Alarm valves Retarding chambers Dry pipe valves Accelerators for dry pipe valves Mechanical sprinkler alarms Electri...

Отзывы: