System
Miscellaneous System Commands
Strata CIX Programming Vol.1 12/09
4-41
System
804 BSIS RS-232 Serial Port Setup
Prerequisite Program:
None
Use this screen to setup the RS-232 serial ports on the BSIS PCB.
1. Select > System > I/O Device.
2. Click the RS232 Serial Port tab.
3. Enter Program 804 data.
4.
Get
Default
sets all values to factory default.
5. Click
Submit
.
F
IELD
D
ESCRIPTION
00 BSIS Port (1~4)
Enter the BSIS PCB port number.
Possible values:1~4 (default = no value)
01 Port Speed
Select the data speed for the BSIS port in bits per second (bps).
Possible values:300, 1200, 2400, 4800, 9600 (default), 19200, 38400 or 57600
Note
The total combined maximum speed of BSIS ports cannot exceed
57,600 bps.
02 Port Parity
Select the parity error checking method used by the BSIS port.
Possible values:None, Even or Odd (default)
03 Data Bits
Select Data Length.
Possible values:7 Bits (default) or 8 Bits
04 Flow Control
This setting indicates the type of flow control used between the BSIS port and
the SMDI or SMDR device. To enable the CIX to buffer call records set this field
to Flow.
Possible values:None (default) or Flow
05 Wait Timer
Select the maximum time to wait for connection. The Timer value can be one
through 255 seconds. Select
0
to set to permanent waiting.
Possible values:0~255 (default = 30)
Summary of Contents for CIX 200
Page 42: ...Network eManager 2 4 Strata CIX Programming Vol 1 12 09 ...
Page 43: ...Network eManager Strata CIX Programming Vol 1 12 09 2 5 Network eManager ...
Page 44: ...Network eManager 2 6 Strata CIX Programming Vol 1 12 09 ...
Page 314: ...This page is intentionally left blank ...
Page 432: ...This page is intentionally left blank ...
Page 434: ...This page is intentionally left blank ...