Extinguishing
Configuring flooding zone control
16
358 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
'Extinguishing sector control' – parameters in the 'Details' tab
Parameters
Value
Description
'Accept commands 'Fire
controls ON/OFF' from
FBF'
On/off
The parameter defines that this control is a fire
control within the meaning of the VdS definition.
When the parameter is activated, all of the control's
effects can be switched off with the corresponding
button on the fire brigade operating panel (FBF).
'Emergency hold button:
when pressed/released,
the pre-discharge warning
time is..'
'..stopped/restarted'
The set time period for the 'Pre-discharge warning
time' starts again after the 'Emergency hold' switch
has been released.
'..continued'
The set time period for the 'Pre-discharge warning
time' starts again after the 'Emergency hold' switch
has been actuated.
'..stopped/resumed' [LU]
After the 'Emergency hold' switch has been released,
the set time period for the 'Pre-discharge warning
time' continues in the same position in which the
switch was activated.
'Minimum duration of
emergency hold' [AT]
On/off, with input field for
time period
Hr:min:sec
Adjustable time period for which the 'Emergency
hold' state should last as a minimum when the
'Emergency hold' switch is actuated. If the switch is
released before the time period elapses, then the
'Emergency hold' state remains in effect for the rest
of the set time period.
'Separate reset of
illuminated warning panel
required' [AT]
On/off
If this is ticked, the illuminated warning indicator
must be reset separately after activation.
Creating cause and effect zones and assigning them to hardware
elements
You will find information on creating and assigning causes and effects within
control elements in chapter 'Assigning elements [
76]'.
See also
2
Configuring an extinguishing control group [
2