Extinguishing
Configuring flooding zone control
16
371 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
Additional standard 'Effects' functions
The table below describes additional standard 'Effects' functions which may be
required on a country-specific basis. They can be created manually and deleted
again if necessary.
Designation
Description
'Illuminated warning panel'
Element type: Illuminated
warning panel
Template ID: '1...'
Function for activating an 'Illuminated warning panel' in the flooding zone.
The function has special parameters which deviate from the standard in the
'Overview' tab. You will find information about the parameters in a separate
section in this chapter.
'Prioritized states' [AT]
Element type: Prioritized
states
Template ID: '1...'
The function allows for a country-specific implementation of an 'Emergency hold'
function. [AT]
The function activates the assigned output depending on certain operating
conditions of the flooding zone. Depending on the operating condition, the system
activates a pre-defined output mode.
Output modes depending on the operating condition:
''Pre-activated' phase': 'Always Off'
''Released' phase': 'Inactive: Off / active: On'
'Emergency hold': 'Always Off'
''Activated' phase': 'Inactive: Off / active: On'
'Mechanically blocked': 'Always Off'
'Automatic release blocked': 'Always Off'
The operating conditions are prioritized should several occur at the same time.
The operating condition with the highest priority activates the output with the
corresponding mode.
Assignment of priorities:
- Priority 0 (highest): ''Pre-activated' phase'
- Priority 1: ''Released' phase'
- Prio 2: 'Emergency hold'
- Prio 3: ''Activated' phase'
- Prio 4: 'Mechanically blocked'
- Prio 5: 'Automatic release blocked'