'Network' task card
Establishing connection from PC to FS720 network
14
327 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
14.2.11.4 Site-specific configuration
For a customer-specific Ethernet network configuration, you have to set 'Type of
redundancy configuration' in the 'Site-specific'.
For the 'Site-specific' configuration, you can configure the following elements
manually:
●
Suppression of ring faults
●
'Redundancy manager'
●
Suppression of port faults
Proceed as described in the previous chapters to configure the individual elements.
14.3 Establishing connection from PC to FS720 network
When the Cerberus-Engineering-Tool is installed, the two routes in the table
below are entered in the PC's network settings.
Network address
Network mask
Gateway
address
Metric
192.168.0.0
255.255.0.0
192.168.200.1
10
192.168.0.0
255.255.0.0
192.168.201.1
10
Table 17: Persistent routes
A connection from the PC to the FS720 network can be established with the
following three variants:
●
Local connection
– The PC is connected to the Ethernet connection of a
standalone or
SAFEDLINK station.
– The PC automatically receives an IP address.
●
Connection to GAP
– The PC is connected to the 'C-WEB/LAN'.
– The PC automatically receives an IP address when the DHCP is configured
GAP.
●
Connection to IP address
– The PC is connected to the 'C-WEB/LAN'.
– The PC's IP address must be set manually.
– If there are external routers between Cerberus-Engineering-Tool and GAP,
the necessary routers must be configured for the C-WEB/LAN and all
SAFEDLINK sub-nets.
The connection can be established using the following menu items:
●
For Cerberus-Engineering-Tool
– 'Commissioning' > 'Download site'
– 'Commissioning' > 'Upload site'
– 'Commissioning' > 'Upload site event memory'
– 'Commissioning' > 'Upload site log files'