'Detection' task card
'Zone'
11
151 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
11.4.2 'Manual zone'
'Manual call points' are evaluated in the 'Manual zone'. The 'Zone' can however
also be configured for inputs or collective detector lines. The danger signals are
evaluated with an OR link. Each manual call point in the 'Zone' can generate an
alarm, but not a
pre-alarm.
You can select between a variety of different templates that are pre-configured for
various applications for the creation of a 'Manual zone'.
The following table shows the properties of the templates along with the event
category and the event text of the message that is generated with an alarm.
Typical application
Typical event category
Event text
1
'Standard':
Evaluation of manual fire detectors
' ----Manual Fire ALARM'
'Manual FIRE ALARM'
'ALARM sub-system':
Evaluation of a sub-system that is
connected via an input
' ----Manual Fire ALARM'
'ALARM sub-system'
'Local ALARM':
Evaluation of manual fire detectors
that generate only a local alarm
' ----Manual Fire ALARM'
'Manual local ALARM'
'Redundancy ALARM':
Evaluation of manual fire detectors
that generate a redundancy alarm
' ----Manual Fire ALARM'
'Redundancy ALARM'
Table 7: Properties of the templates
1
Text that is shown on the display of the Person Machine Interface when the event
occurs.
11.4.3 'Technical zone'
In 'Technical zone', inputs for
technical messages, e.g., fault or danger by
extraneous equipment, are evaluated.
You can select between a variety of different templates that are pre-configured for
various applications for the creation of a 'Technical zone'. The following table
shows the properties of the templates along with the event category and the event
text of the message that is generated with an event. The templates are all with
single-detector dependency and without 'Pre-ALARM'.
Main features and typical application
Typical event category
Event text
1
'Standard (ack./latching)':
The event must be acknowledged with
latching
' --Other technical message'
'Technical message'
'Standard (ack./non-latching)':
The event must be acknowledged
without latching
' --Technical message:
programmable'
'Technical message'
'Fault sub-system':
Evaluation of fault messages of a
connected sub-system
' --Other fault'
'Fault sub-system'
'Sub-system OFF':
Evaluation of switched off messages of a
connected sub-system
' --Sub-system isolation'
'Sub-system OFF'