10.3.6 Alarm sounder and interbase
You can configure the properties for the acoustic and optical alarming for the
following devices:
●
Alarm sounder FDS221
●
Alarm sounder with supplementary optical indication FDS229
●
Sounder interbase DBS721
●
Sounder beacon interbase DBS728 and DBS729
Setting properties of the alarm sounders and interbases
1. Select the 'Hardware' task card.
2. In the tree view, open the
'Station' > the
line card > the
loop or the
stub.
3. Open the element for one of the devices mentioned above.
4. Highlight the element 'Sounder' or 'Sounder beacon'.
5. Set the properties you want in the detail editor. The properties are described in
the following sections.
Figure 32: Properties in the detail editor of the element 'Sounder'
Figure 33: Properties in the detail editor of the element 'Sounder beacon'
'ALERT tone'
This setting specifies the tone in the 'Alert' mode.
'EVAC tone'
This setting specifies the tone in the 'Evac' mode.
'Sounder volume'
This setting specifies the sound level in the activated status.
'Beacon activation'
This setting specifies the activation mode of the beacon.
This property is available only for DBS728, FDS229, and DBS729.