'Audio sequence'- parameters
Parameters
Values
Description
'Audio stop mode'
‒
The parameter determines when the system
terminates a current audio sequence when the
activating cause group is deactivated.
Information: If several cause groups are active at the
same time, the system always plays the audio
sequence of the cause group with the highest
priority.
Information: If the operating personnel actuates
'Alarm device' on the PMI, then the system
terminates the current audio sequence immediately,
regardless of the setting for the 'Audio stop mode'
parameter.
Information: If the 'Walk test' function activates an
audio sequence, then the system terminates the
audio sequence immediately when the set time
elapses in the 'Duration of voice sounder activation
in walk test' parameter. This is independent of the
setting for the 'Audio stop mode' parameter.
The following options can be configured:
'Immediately upon
deactivation of the cause
group'
●
The audio sequence is stopped immediately if
the associated cause group is no longer active.
Information: If other cause groups are active at
this time, the system immediately plays the audio
sequence of the active cause group with the
highest priority.
'When audio sequence
ends (if no other cause
group is active/activated)'
●
The audio sequence is played until it has ended,
even if the associated cause group has since
deactivated.
Information: In two exceptional cases, the
system terminates the current audio sequence
immediately:
1. Other cause groups are active when the cause
group is deactivated. In this case, the system
immediately plays the audio sequence of the
active cause group with the highest priority.
2. One or more cause groups have been
activated between the deactivation of the cause
group and the end of the associated audio
sequence. In this case, the system immediately
plays the audio sequence of the active cause
group with the highest priority.
'Beacon activation'
'Enabled'
The sounder's integrated beacon is also activated
when the voice message is active.
Information: The voice sounder FDS227 as well as
the voice sounder base FDSB227 have an integrated
beacon.
'Enabled, 1s delayed'
The integrated beacon of the sounder is activated
with a delay of one second after the voice message.
' - (disabled/no activation)' The sounder's beacon remains inactive when the
voice message is activated.