'Control' task card
Evac control group
12
215 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
5. Leave the 'Delay' parameter for the 'Section' elements or the 'Detection area'
element at '00:00:00' as immediate warning is required on each floor.
6. Use multiselection to select all 'Section' elements or the 'Detection area'
element under the 'Causes ALERT' element and copy these using the 'Copy'
function.
7. In the 'Phased sounder evac control'/'Phased voice evac control' element,
highlight the 'Causes EVAC' element or the 'Causes EVAC FIRE
(+DEGRADED MODE)' element.
8. Use 'Paste' to add the copied 'Section' elements or the 'Detection area' element
to the 'Causes EVAC' element or the 'Causes EVAC FIRE (+DEGRADED
MODE)' element.