Extinguishing
Configuring flooding zone control
16
377 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
Parameters
Values
Description
'Activation delay'
Input field for time period
[Hr:min:sec]
Defines the period of time for which the
activation of the 'Effects' function is
delayed.
The max. delay time is 30 minutes.
'Deactivation state'
'Quiet'
Defines the state in which the
extinguishing system must be for the
control to deactivate the 'Effects' function
again.
Prerequisite:
'Specific deactivation state' has been
selected for the 'Reason for deactivation
parameter'.
The parameter is specified in the relevant
function template and cannot be
adjusted.
All possible states of the 'Activation
state' parameter. See above.
'Deactivation delay'
Input field for time period
[Hr:min:sec]
Defines the period of time for which the
deactivation of the 'Effects' function is
delayed. As a prerequisite, the 'Specific
deactivation state' value must be selected
for the 'Reason for deactivation'
parameter.
The max. delay time is 30 minutes.
'Reason for deactivation'
'Specific deactivation state'
Defines the reason for the deactivation of
the 'Effects' function.
The parameter is specified in the relevant
function template and cannot be
adjusted.
'When leaving activation state'
'Timeout defined with 'Activation
duration''
'Activation duration'
Input field for time period
[Hr:min:sec]
Defines the period of time after which an
active 'Effects' function is automatically
deactivated again.
Prerequisite:
'Timeout defined with 'Activation duration''
has been selected for the 'Reason for
deactivation' parameter.
'Interruptible by reset'
On/off
If this is ticked, the activation of the
'Effects function can still be reset during
the pre-defined duration of activation with
'Reset'. Otherwise, the state can only be
reset after the duration of activation has
elapsed.
'Activated on reset'
On/off
If this is ticked, the effect and the
'Activation duration' timer are activated
after resetting with 'Reset'.