'Detection' task card
'Zone'
11
149 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
Main features and typical application
Typical event category
Event text
1
'Single, local ALARM':
●
Single-detector dependency
●
With 'Pre-ALARM'
●
Only the local alarming is activated in
'MAIN STAGE'
●
'PRE-STAGE':
– ' --Pre-ALARM, fire'
●
'MAIN STAGE':
– ' ------General autom. Fire
ALARM'
●
'PRE-STAGE':
– 'Pre-ALARM'
●
'MAIN STAGE':
– 'Autom. local ALARM'
'Multi, standard':
● ↑
Multi-detector dependency
●
With 'Pre-ALARM'
●
'PRE-STAGE':
– ' --Pre-ALARM, fire'
●
'MAIN STAGE':
– ' ------General autom. Fire
ALARM'
●
'PRE-STAGE':
– 'Pre-ALARM'
●
'MAIN STAGE':
– 'Autom. FIRE ALARM'
'Multi, garage':
●
Multi-detector dependency
●
Without 'Pre-ALARM'
' ------General autom. Fire ALARM' 'Autom. FIRE ALARM'
'Multi, store':
●
Multi-detector dependency
●
With 'Pre-ALARM'
●
Only the local alarming is activated in
'MAIN STAGE'
●
'PRE-STAGE':
– ' --Pre-ALARM, fire'
●
'MAIN STAGE':
– ' ------General autom. Fire
ALARM'
●
'PRE-STAGE':
– 'Pre-ALARM'
●
'MAIN STAGE':
– 'Autom. FIRE ALARM'
'Multi, 2 det. dependency':
●
Multi-detector dependency
●
With 'Pre-ALARM'
●
'PRE-STAGE':
– ' --Pre-ALARM, fire'
●
'MAIN STAGE':
– ' ------General autom. Fire
ALARM'
●
'PRE-STAGE':
– 'Pre-ALARM'
●
'MAIN STAGE':
– 'Autom. FIRE ALARM'
'Multi, ALARM sub-system':
●
Multi-detector dependency
●
With 'Pre-ALARM'
●
'PRE-STAGE':
– ' --Pre-ALARM, fire'
●
'MAIN STAGE':
– ' ------General autom. Fire
ALARM'
●
'PRE-STAGE':
– 'Pre-ALARM'
●
'MAIN STAGE':
– 'ALARM sub-system'
'Multi, 2 det. dependency II' [AT]:
●
Multi-detector dependency
●
With 'Pre-ALARM'
●
Only the local alarming is activated in
'PRE-STAGE'
●
'PRE-STAGE':
– ' ------Autom. First ALARM'
●
'MAIN STAGE':
– ' ------General autom. Fire
ALARM'
●
'PRE-STAGE':
– 'Autom. FIRST ALARM'
●
'MAIN STAGE':
– 'Autom. FIRE ALARM'
'Multi, 2 det. dependency III' [CH]:
●
Multi-detector dependency
●
With 'Pre-ALARM'
●
'PRE-STAGE':
– ' ------Autom. First ALARM'
●
'MAIN STAGE':
– ' ------General autom. Fire
ALARM'
●
'PRE-STAGE':
– 'Autom. FIRST ALARM'
●
'MAIN STAGE':
– 'Autom. FIRE ALARM'
'Two-zone dependency'
●
With 'Pre-ALARM'
●
Only the local alarming is activated in
'PRE-STAGE'
●
'PRE-STAGE':
– ' ------Autom. First ALARM'
●
'MAIN STAGE':
– ' ------General autom. Fire
ALARM'
●
'PRE-STAGE':
– 'Autom. FIRST ALARM'
●
'MAIN STAGE':
– 'Autom. FIRE ALARM'
Table 5: Properties of the templates
1
Text that is shown on the display of the Person Machine Interface when the event
occurs.