Connectivity and communication with 'Station'
Load data to the station
7
106 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
7.4 Load data to the station
Data is loaded from Cerberus-Engineering-Tool to the
'Station' when the
following commands are performed.
●
'Initialize station'
●
'Download site'
If you use more than one network cards on the PC, observe the information
contained in chapter 'IP settings for several network cards [
The table below shows which data is overwritten in the 'Station'.
Command
Overwrites the
Sets the address
of the 'Station'
Overwrites the
configuration
'Initialize station'
1
Yes
Yes
Yes
'Download site'
Yes
No
Yes
2
1
Command is only performed for the 'Station' that is connected to the PC via LAN.
2
The configuration of selected 'Stations' or all 'Stations' in the
'Site' can be
overwritten as an option.
See also
2
7.5 Initializing the station
●
Each
'Station' in a system with several networked 'Stations' must have a
unique address.
●
Once a 'Station' has been started for the first time or once the firmware on the
main CPU has been updated, a 'Station' has the address '1'. Networked
'Stations' must therefore all be initialized.
●
If two 'Sites' are merged to form one
'Site', the 'Stations' with the same
addresses in the added 'Site' must each be given a new address.
●
The 'Initialize station' procedure issues the 'Station' an address within the 'Site'
according to the configuration in Cerberus-Engineering-Tool.
A
standalone 'Station' does not have to be initialized.
If you use more than one network cards on the PC, observe the information
contained in chapter 'IP settings for several network cards [
You will find a detailed description for initialization of a 'Station' in document
'A6V10210416'. See chapter 'Applicable documents'.
See also
2
Loading configuration from the PC to the station [
2