'Hardware' task card
C-NET detector line
10
133 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
'Enable temporary freeze of output position'
If the checkbox is checked, the 'Freeze selected outputs ON' command is available
for the output. The position of the output is not changed if the
'Station' or line is
restarted, a configuration is loaded to the 'Station', or a module is reset.
See also
2
Collective detector line via input/output module FDCIO223
2
Sounder line via input/output module FDCIO223 [
2
Input/output module FDCIO223 with monitored input/output
2
10.3.10 Zone module FDCI723
The zone module FDCI723 is operated on the 'C-NET' and has one input. The
following
detector lines can be connected to the input:
● ↑
Collective detector line
●
Collective detector line for areas at risk of explosion (zones 1 and 2)
●
Conventional detector line
Setting the properties of the 'Collective' element
1. Select the 'Hardware' task card.
2. In the tree view, open the
'Station' > the
line card > the
loop or the
stub.
3. Open the element 'FDCI723'.
4. Highlight the element 'Collective'.
5. Set the properties you want in the detail editor.
The properties are described in the following sections.
Figure 39: Properties in the detail editor for the
physical channel of the zone module