Connectivity and communication with 'Station'
Loading event memory to PC
7
109 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
3. Select the 'Stations' whose configuration you would like to load to Cerberus-
Engineering-Tool and click on 'Start'.
a
The 'Action confirmation' window opens.
4. Click on 'Yes'.
a
The configuration is loaded to the PC.
a
The progress is displayed in the 'Upload site' window.
7.8 Loading event memory to PC
The 'Upload site event memory' can be used to load the event memory of one or
'Stations' in the
'Site' from any 'Station' to the PC.
w
A valid 'Site' is loaded.
w
BDV version and the same global configuration
so that site-wide communication is supported.
w
'Station' and Cerberus-Engineering-Tool must belong to the same
organizational unit.
w
The PC is connected to a 'Station' in the 'Site' via an Ethernet cable.
1. In the 'Commissioning' menu, select the 'Upload site event memory' menu item.
a
The 'Connect' window opens.
2. Select the connection setting and confirm with 'OK'.
a
The selection window opens.
3. Select the 'Stations' whose event memory you would like to load to the PC.
4. Determine the memory location and the file name.
5. Click on 'Start'.
a
The data is transferred.
a
The status of the transfer is shown in the status bar.
a
The data is saved as a CSV file the specified location.
7.9 Loading the site log files to the PC
You can load log files of individual 'Stations' of a 'Site' to the PC. The log files are
stored in a compressed archive that is determined by the user. The archive
contains a folder for each 'Station'.
Example:
LogFilesArchiveExample.zip
\Station1\
syslog_0.log
syslog_1.log
syslog_2.log
\Station2\
syslog_0.log
syslog_1.log