'Detection' task card
'Zone'
11
158 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
Sub-element of 'XC10
zone'
Input or output on
FDCIO222
Function
Input 'Discharged'
IN1
Activating or resetting the
extinguishing release
Input 'Fault'
IN2
Fault message
Input 'Pre-alarm'
IN3
Activating or resetting the
extinguishing pre-alarm
Input 'Blocked'
IN4
Blocking or enabling the
extinguishing release
Output 'Reset'
OUT A
Resetting the extinguishing
release
Output 'Block
autom.+manual'
OUT B
Blocking the automatic and
manual extinguishing release
Output 'Block autom.' OUT C
Blocking the automatic
extinguishing release
'Input 'Discharged''
The extinguishing control panel detects the activation or resetting of the
extinguishing release by activating or deactivating 'Input 'Discharged''.
When 'Input 'Discharged'' is activated, the FC720 displays the message 'Exting.
discharged'. The activation of the extinguishing release is displayed as an alarm
and the
AVC is started.
The message does not disappear automatically when 'Input 'Discharged'' is
deactivated, i.e. when a reset is made on the extinguishing control panel. The
message must be acknowledged and reset on the FC720.
'Input 'Fault''
The extinguishing control panel detects the occurrence or disappearance of a fault
by activating or deactivating 'Input 'Fault''. When 'Input 'Fault'' is activated, the
FC720 displays a fault message.
The message does not disappear automatically when 'Input 'Fault'' is deactivated,
i.e. when the fault indication disappears on the extinguishing control panel. The
message must be acknowledged on the FC720.
'Input 'Pre-alarm''
The extinguishing control panel detects the activation or resetting of the
extinguishing pre-alarm by activating or deactivating 'Input 'Pre-alarm''.
When 'Input 'Pre-alarm'' is activated, the FC720 displays the message 'Exting. pre-
alarm'. The activation of the extinguishing pre-alarm is displayed as an alarm and
the AVC is started.
The message does not disappear automatically when 'Input 'Pre-alarm'' is
deactivated, i.e. when a reset is made on the extinguishing control panel. The
message must be acknowledged and reset on the FC720.
'Input 'Blocked''
The extinguishing control panel detects the blocking or releasing of automatic and
manual extinguishing release by activating or deactivating 'Input 'Blocked''.
The blocking is indicated as isolation on the FC720
Person Machine Interface.