'Detection' task card
Collective detector line via input/output module FDCIO223 or zone module
11
170 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
11.7 Collective detector line via input/output module
FDCIO223 or zone module
You can use the following elements to connect
collective detector lines:
●
Inputs/outputs of input/output module FDCIO223
●
Input of the zone module FDCI723
To do this, you must assign the
physical channel of the FDCIO223 or the
'Zone'.
Assigning a collective detector line
1. Select the 'Detection' task card.
2. Open
'Station' >
'Area' >
'Section' in the tree view.
3. Highlight a 'Zone'.
4. In the menu bar, click on 'Assign'.
a
The 'Assign dialog' window opens.
5. Select 'Collective' at the left in the window.
a
The 'Hardware tree' is depicted at the right of the window. The elements
that can be assigned are highlighted.
6. Open the FDCIO223 input/output module and select
'Collective/input/sounder/output'.
– or
7. Open the zone module FDCI723 and select 'Collective'.
8. Click on 'Assign'.
a
'Collective/input/sounder/output' or 'Collective' is assigned to the 'Zone'.