'Control' task card
Evac control group
12
204 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
'Phased sounder evac control' – 'Causes' assignments – parameters
in the 'Overview' tab
The parameters described below are not available or cannot be configured in
every 'Causes' assignment.
The following table describes possible parameters in the 'Overview' tab for
'Causes' assignments:
Parameters
Values
Description
'Delay'
Input field for time period
[hh:mm:ss]
Adjustment range: 0...120
min
Increments: 30 sec
The parameter determines the length of the
activation delay by the control for the respective
effects when the activation conditions of the
assigned cause have been met.
Example: If, for example, an input is assigned as the
cause and the control evaluates it as 'active', then
the activation condition of this cause has been met.
The control delays the activation of the relevant
control effects from this point by the time set in this
parameter.
'Evaluation filter time'
Input field for time period
[hh:mm:ss]
Adjustment range: 0...5
min
Increments: 1 sec
This parameter specifies the length of time the signal
of the assigned input must be active until the control
evaluates it as active.
'Phased sounder evac control' – 'Effects' assignments – parameters
in the 'Overview' tab
The following table describes possible parameters in the 'Overview' tab for 'Effects'
assignments:
Parameters
Values
Description
'Enabled'
On/off
Activates or deactivates the 'Activation timeout
'manned'' parameter.
'Activation timeout
'manned''
Input field for time period
[hh:mm:ss]
Adjustment range: 0...100
min
Increments: 1 sec
The parameter specifies the time that needs to
elapse in 'Manned' operation before the assigned
alarm device is automatically deactivated again.
'Enabled'
On/off
Activates or deactivates the 'Activation timeout
'unmanned'' parameter.
'Activation timeout
'unmanned''
Input field for time period
[hh:mm:ss]
Adjustment range: 0...100
min
Increments: 1 sec
The parameter specifies the time that needs to
elapse in 'Unmanned' operation before the assigned
alarm device is automatically deactivated again.
See also
2