'Hardware' task card
Onboard I/Os
10
119 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
10.1.2 Configuring permanent access for Cerberus-Remote
Permanent access has to be configured for each
'Site'.
Configuring permanent access means that access at the 'Station' is not required.
You will find more information on the Cerberus-Remote operation modes in
Configuring permanent access
1. Select the 'Hardware' task card.
2. Select the 'Station' for which you wish to configure permanent access for
Cerberus-Remote.
3. Select the 'Cerberus-Remote' tab in the detail editor.
4. Select the operation mode in the 'Permanent Cerberus-Remote access' field.
5. Load the configuration from the PC to the station.
a
Permanent access is configured.
Figure 26: Configuring the operation mode for Cerberus-Remote
Indicating permanent access
The 'Indicate permanent Cerberus-Remote access' checkbox specifies whether
permanent access of Cerberus-Remote is indicated at the 'Station' with a message.
10.2 Onboard I/Os
The following inputs / outputs are available on the periphery board:
●
'I/O': Configurable inputs / outputs (24 V)
●
'RT fire/NOT monitored': Connection of an
RT channel for RT alarm
●
'RT fire/monitored': Monitored output for RT Alarm
●
'RT fault/NOT monitored': Connection of an RT channel for RT Fault
●
'RT fault/monitored': Monitored output for RT Fault
●
'Sounder/monitored': Monitored sounder output
These inputs and outputs are shown in the
'Hardware tree' under the 'Periphery
board' element.
You will find information on the settings in the detail editor of the inputs / outputs in
If the output is assigned to the
effect of a control, you can set additional
properties in the 'Control' tab of the detail editor. You will find a description of these
settings in chapter 'Properties of the assigned effect elements [