'Control' task card
Alarming control group
12
180 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
12.2.2 Properties of the assigned effect elements
You can set additional properties in the assigned effect elements of an
alarming
control. The settings are described in the following sections.
If the
effect is assigned to an RT channel, you can set the following:
Figure 62: Settings in the detail editor of an assigned RT channel
'OFF allowed while AVC active (t1/t2)'
This setting specifies whether the
RT channel may be switched off while the
AVC is active i.e., while the times t1 and t2 are running.
Independent of this setting, the 'ÜE ab' command is always executed by a fire
brigade operating panel (FDOP).
'Minimal duration of activation'
This setting specifies the minimum period during which the
RT channel remains
active even if the cause for triggering is no longer available.
If the effect is assigned to a sounder line, you can set the following:
Figure 63: Settings in the detail editor of an assigned sounder line