'Control' task card
Evac control group
12
219 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
Configuring prioritized voice evac. control
The sequence only contains the necessary configuration steps. You will find
information about the elements that can be assigned or created, as well as the
parameters, in separate sections further down in this chapter.
NOTICE
Incorrect cause assignment for 'Activation timeout 'manned'' / 'Activation timeout
'unmanned''
The 'Activation timeout 'manned'' / 'Activation timeout 'unmanned'' sounder
property is only evaluated for one 'Area' element in the detection tree or for
elements within one 'Area' element.
w
One or more sounders are assigned as 'Control'
element effects.
w
The 'Activation timeout 'manned'' property and / or 'Activation timeout
'unmanned'' is active.
●
Only assign one 'Area' element or elements from one 'Area' element as the
cause of the 'Control'.
w
An 'Evac control group' element is created in the 'Control tree'.
1. For each separate building zone to be evacuated, create a 'Prioritized voice
evac control' element under the 'Evac control group' element. This could be a
single floor, for example.
a
The configuration tool creates the element with predefined 'Causes'
elements.
2. Configure the 'Prioritized voice evac control' element in the 'Overview' and
'Details' tabs.
3. If necessary, adjust the customer text in the 'Overview' tab.
4. Remove any 'Causes' elements that are not needed.
Information: The 'Causes EVAC FIRE (+DEGRADED MODE)' element is an
essential part of a 'Prioritized voice evac control' element and cannot be
removed.
5. Add the required 'Causes' elements.
6. If necessary, create a customer text in the 'Overview' tab for each 'Causes'
element.