'Operation' task card
Global system configuration
13
256 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
Properties for 'Global behaviour' on the 'Details' tab
'Type of address information'
This setting specifies which address information is displayed in messages: Plan no.
and/or element address. The setting is depending on the element and on the
availability of the plan no.
'BACnet alarm notification in section enabled'
If this checkbox is checked, a BACnet notification or 'Section summary' is created if
an alarm occurs within an FS720 section. The BACnet object type of the 'Section
summary' is 'Binary Value'. The 'Section summary' can be transmitted to sub-
systems, e.g., to Desigo PX.
'BACnet notifications of detector lines enabled'
If this checkbox is checked, a BACnet notification is created if a fault or information
event occurs on an FS720 detector line or on a device within the detector line. A
'Line fault summary' or 'Line information summary' is created, the BACnet object
type of which is 'Life-Safety'.
'BACnet priority of Fire/Smoke extraction dampers, commanding via
control'
This setting defines the BACnet priority for fire and smoke dampers when the
dampers are controlled automatically by damper controls.
'BACnet priority of Fire/Smoke extraction dampers, commanding via
Operating terminal'
This setting defines the BACnet priority for fire and smoke dampers when the
dampers are controlled manually via an operating terminal.
'Enabled'
This setting specifies whether a reminder message is displayed before the 'Time
limited isolation' of a 'Zone' or a 'Detector' expires and the 'Zone' or the 'Detector' is
switched back on again automatically.