'Network' task card
Checklist for network and BACnet configuration
14
341 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
Checklist for BACnet configuration
Figure 162: Example of BACnet configuration
Element in the structure tree
Configuration in the detail editor
Required setting/value
'Global BACnet configuration'
'Enable BACnet communication' Activated
'BACnet character set'
UCS-2
'Address range, lower limit'
0
'Address range, upper limit'
4194302
'Suppress BACnet mode ‘OFF’ in
channels'
Deactivated
Creating 'BACnet client
configuration'
Several clients possible
'BACnet client configuration'
'BACnet device ID'
Enter
'Check BACnet client address'
Depending on network configuration
'BACnet network no.'
0
'BACnet IP address'
Depending on network configuration
'BACnet UDP port'
47808
'BACnet device object' (on every
'Station')
'BACnet UDP port'
47808
'APDU timeout'
00:00:10
'No. of APDU retries'
3
'APDU segment timeout'
00:00:05
'BACnet device object' (only on one
'Station')
'Enable BBMD'
Activated
'Enable FDT'
Deactivated
'Two hops'
Activated
'No. of FDT entries'
2