'Network' task card
Network configuration
14
317 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
5. Highlight all 'Fx72x/SAFEDLINK one after the other.
6. Enter the IP address in the 'Overview' tab of the detail editor.
See also
2
Setting network speed for SAFEDLINK [
14.2.6 Entering routes for external access to extended networks
via GAP
In order that a PC or a
management station from an external network has access
'Stations' in the extended network via router and
entered in the GAP and in the Ethernet sub-net.
Although all network addresses in this chapter are examples, they are consistent.
Function of the route in the GAP
The route in the GAP is required for the following situations:
There is a 'Security module (firewall) FN2009-A1' router between the extended
network in the fire detection system and the external network.
●
'Destination address' of the route is 'Cerberus-Engineering-Tool' and/or the
management stations
● ↑
'Gateway' is the FS720 address of the 'Security module (firewall) FN2009-A1'
router
Function of the route in the Ethernet sub-net
The route in the Ethernet sub-net is required for the following situations:
The extended network in the fire detection system has a standby router.
There is a 'Security module (firewall) FN2009-A1' router between the extended
network in the fire detection system and the external network.
●
'Destination address' of the route is 'Cerberus-Engineering-Tool' and/or the
management stations
●
'Gateway' is the Ethernet address of the GAP
Additional conditions for access
●
GAP must be connected to 'C-WEB/LAN'.
●
'Security module (firewall) FN2009-A1' must be configured.