'Hardware' task card
I/O cards
10
135 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
Operation mode
'Mains
supervision
enabled'
'Battery
supervision
enabled'
'Converter
supervision
enabled'
Display delay
'Emergency
power delay',
'Enabled'
With battery
backup
√
√
√
√
or –
Without battery
backup
√
–
√
–
With an external
DC power supply
unit
–
–
–
–
With redundant
supply
√
√
–
√
or –
Table 4: Configuration of the power supply
√
Checkbox checked
–
Checkbox unchecked
You will find the hardware configuration in document A6V10210416. See chapter
'Applicable documents'.
See also
2
10.5 I/O cards
I/O card (programmable) FCI2008-A1
The I/O card (programmable) FCI2008-A1 has 12 programmable inputs / outputs.
I/O card (remote transmission) FCI2007-A1
The I/O card (remote transmission) FCI2007-A1 has eight inputs / outputs for alarm
and fault transmission.
I/O card (horn/monitored) FCI2009-A1
The I/O card (horn / monitored) FCI2009-A1 has eight monitored outputs for alarm
and fault transmission.
You will find additional information on the I/O cards in document A6V10210368.
See chapter 'Applicable documents'.
Create I/O card
1. Select 'Hardware' >
'Station' in the task card.
2. Create the I/O card for the 'Station'. Link [