Extinguishing
Configuring the forwarding of the extinguishing released state
16
395 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
18. Use 'Assign' to assign the 'Fire control' element no. 2 to the 'Auxiliary function
off' element as the cause. To do this, select the 'All activations' event category
on the left in the 'Assign' dialog and then select the 'Fire control' element no. 2
on the left in the control tree.
a
The forwarding of the 'Released' state to an output is configured.
Settings in the 'Details' tab
The table below shows the required settings in the 'Details' tab for both universal
controllers in order to forward the 'Released' state of a flooding zone.
Parameters
'Fire control' element no. 1 for recording
the 'Released' state
'Fire control' element no. 2 for
transmitting the 'Isolation' state
'Accept commands 'Fire
controls ON/OFF' from
FBF'
Off
Off
'Controls a 'door holders'
application'
Off
Off
''Activation' events hidden'
On
On
'OFF allowed'
Selection: 'Always'
Selection: 'Never'
'DEACTIVATION allowed'
Selection: 'NOT if activated
automatically by causes'
Selection: 'NOT if activated
automatically by causes'
'Reactivation upon
unsuccessful reset'
On
On
'Control test allowed'
Off
Off
See also
2
Configuring flooding zone control [
2
Configuring an extinguishing reporting zone [
2