'Control' task card
Evac control group
12
201 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
w
An 'Evac control group' element is created in the 'Control tree'.
1. For each separate building zone to be evacuated, create a 'Phased sounder
evac control' element under the 'Evac control group' element. This could be a
single floor, for example.
a
The configuration tool creates the element with predefined 'Causes'
elements.
2. Configure the 'Phased sounder evac control' element in the 'Details' tab.
3. If necessary, adjust the customer text in the 'Overview' tab.
4. Assign the required events to the 'Causes EVAC' and 'Causes ALERT'
elements with 'Assign'. For the 'Causes ALERT' element, this can be a fire
alarm in a detection zone, for example. Alternatively, you could also assign an
input signal.
Tip: Use multiselection to highlight multiple assignable elements in the dialog
window. This saves time if you want to assign an event or an event category
from several detection zones or sections to the cause group.
Tip: You can use multiselection to highlight several events or event categories
for an assignable element and assign these as causes. You can also select
predefined event groups on the left side of the dialog under 'Grouped type
selection'.
5. Configure all assigned causes within a 'Causes' element in the 'Overview' tab.