14 'Network' task card
Configure the network settings for the fire detection system in the 'Network' task
card.
You will find all permissible networking types and the required network settings
described in detail in document 'A6V10210362'.
You will find pre-conditions for configuration and the required work steps in
document 'A6V10210416'. See chapter 'Applicable documents'.
The following chapter describes the corresponding configuration in Cerberus-
Engineering-Tool.
See also
2
14.1 Network parameters
You will find details of the ports in FS720 in document A6V101039439. See
chapter 'Applicable documents'.
14.2 Network configuration
14.2.1 Creating networked 'Stations'
Networked
'Stations' must be assigned to the 'Ethernet' or 'SAFEDLINK' sub-net:
''New station' window, 'Ethernet station' or 'SAFEDLINK station' option.
In the 'Network' task card, references for 'Stations' are automatically created under
the 'Global system configuration' > 'FS720 network configuration' > 'Ethernet sub-
net' elements.
IP addresses for Ethernet and
router stations
IP addresses ranging from 192.168.200.0…192.168.200.255 to
192.168.255.0…192.168.255.255 are reserved in FS720 can cannot be used.
Ethernet 'Stations'
The 'Fx72x/Ethernet' references for all
Ethernet 'Stations' can be found in the
'Connections' element under 'Ethernet sub-net'.
SAFEDLINK 'Stations'
The 'SAFEDLINK sub-net' element is automatically created under 'Ethernet sub-
net'. The 'Fx72xSAFEDLINK' references for all
SAFEDLINK-'Stations' can be
found in the 'Connections' element underneath it.
If the SAFEDLINK 'Stations' are split into several sub-nets, more 'SAFEDLINK sub-
net' elements can be created using the 'New element' function.