'Hardware' task card
C-NET detector line
10
127 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
Sounder element – parameters in the 'Overview' tab
Parameters
Value
Description
'Custom audio library ID'
Indicator field
[0]: Standard audio library
[1...2047]: No. of the user-
defined audio library
Note: The audio library can
be imported by the sounder
in question and cannot be
changed in the
configuration. The input
field is grayed out.
The audio library displays the parameter that the
sounder in question is using.
Note: The configured ID number in the allocated
control element must match the number displayed in
this field. You will find additional information on this
in chapters 'Phased voice evac. control [
205]' and
'Prioritized voice evac. control [
'Voice sounder' / 'Voice sounder beacon' elements – parameters in
the 'Overview' tab
The elements 'Voice sounder' and 'Voice sounder beacon' do not have all the
parameters described in the table below.
Parameters
Value
Description
'Beacon activation'
'Alert + Evac'
The parameter defines the events for which the
beacon is activated.
Information: Parameter values in brackets are
outside the authorized range.
The following settings are possible:
●
The system activates the beacon in the following
events: 'Alert' or 'Evac'
'Alert + Evac, 1s delayed'
●
The beacon is activated using the same method
as 'Alert + Evac' but with a one-second delay.
'Evac'
●
The system activates the beacon in the following
events: 'Evac'
'Evac, 1s delayed'
●
The beacon is activated using the same method
as 'Evac' but with a one-second delay.
' - (disabled/no activation)'
●
The beacon remains deactivated at all times.
'Beacon intensity'
'High'
The parameter defines the intensity with which the
beacon lights up.
Information: Parameter values in brackets are
outside the authorized range.
'Medium'
'Low'
'(Indicator mode)'
'Beacon self-test enabled' On/off
The parameter defines whether the sounder's or
sounder base's self-test function is active.
The self-test function triggers a weak flash every few
seconds to check that the light is functional.
Deactivate the function for applications where this
function could be a distraction or disruption.