'Control' task card
Evac control group
12
200 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
The table shows the configurable phased evac. controls:
Evac control
Description
'Phased sounder evac
control'
Element for configuring a phased evac. control with
alarm devices that can only play tones. You will find
more information on this phased evac. control in
chapter 'Phased sounder evac. control [
'Phased voice evac control' Element for configuring a phased evac. control with
sounders that can play voice messages in addition
to the alarm tones. This phased evac control also
provides extra functions, such as the rule-based
playing of a school bell.
You will find more information on this phased evac.
control in chapter 'Phased voice evac. control
12.4.2.1 Phased sounder evac. control
Phased sounder evac. controls are configured with the 'Phased sounder evac
control' element within an 'Evac control group' element. These controls are for
evac. applications with alarm devices which can only play 'Alert' tones and 'Evac'
tones. You will find information on controls for alarm devices that can also play
voice messages in chapter 'Phased voice evac. control [
A 'Phased sounder evac control' element has the following configuration options:
●
Assignment of causes to the 'Causes ALERT' cause group for the 'Alert'
evacuation phase
●
Assignment of causes to the 'Causes EVAC' cause group for the 'Evac'
evacuation phase
●
Configuring an activation delay for each assigned cause, e.g., depending on
the location at which the cause was triggered
●
Configuring the alarm devices that should be activated when a cause group is
activated
Configuring phased sounder evac. control
The sequence only contains the necessary configuration steps. You will find
information about the elements that can be assigned or created, as well as the
parameters, in separate sections further down in this chapter.
NOTICE
Incorrect cause assignment for 'Activation timeout 'manned'' / 'Activation timeout
'unmanned''
The 'Activation timeout 'manned'' / 'Activation timeout 'unmanned'' sounder
property is only evaluated for one 'Area' element in the detection tree or for
elements within one 'Area' element.
w
One or more sounders are assigned as 'Control'
element effects.
w
The 'Activation timeout 'manned'' property and / or 'Activation timeout
'unmanned'' is active.
●
Only assign one 'Area' element or elements from one 'Area' element as the
cause of the 'Control'.