Extinguishing
Configuring flooding zone control
16
367 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
'Causes' functions – parameters in the 'Details' tab
The error handling in the 'Details' tab only works for causes which are connected
to the extinguishing card directly. The error behavior of causes, which are not
connected to the extinguishing card directly, must be configured in a special
'Causes' function, such as 'Fault -> 'Block autom. release''.
Parameters
Values
Description
'Fault behaviour [EN
12094-1 requirements: see
tooltip]'
NOTICE! Changes to this
parameter can lead to error
behavior which does not
correspond to the standard
specifications. Only
change this parameter if
the change complies with
the standard specifications.
'Block autom.+man. release'
In the event of an error, the site switches
automatically into the 'Block
aumanual release' operation mode at
the allocated input of the 'Causes' function.
'Block autom. release'
In the event of an error, the site switches
automatically into the 'Block automatic release'
operation mode at the allocated input of the
'Causes' function.
'Activate but don't release'
In the event of an error, the site activates an
extinguishing process at the allocated input of
the 'Causes' function but does not trigger
extinguishing.
'No blocking'
In the event of an error, the site does not block
the automatic or manual activation of
extinguishing at the allocated input of the
'Causes' function.
Assigned 'Input' elements – parameter in the 'Overview' tab
Parameters
Values
Description
'Activation/deactivation
filter time'
Input field for time period
[hh:mm:ss]
The parameter determines the length of time
that a signal needs to be applied to the input
for this to be evaluated as 'active' and how
long the signal must have been removed for
the input to be evaluated as 'inactive'.
The following lengths of time can be adjusted:
0...1 min
NOTICE! The filter cannot be configured in
every case as immediate activation is required
with certain functions.
'Delay of 'Incorrect state'
event'
Input field for time period
[hh:mm:ss]
Determines the period of time during which the
input must have reached the opposite state
after the switching condition has been
reached. The 'Incorrect state' event is issued if
the input does not reach the opposite state in
the set time.
The 'Extinguishing input type' of the assigned
input must be 'Simple switchable'. You will find
more information about configuring the
'Extinguishing input type' in chapter
'Configuring inputs and outputs [
will find information about circuitry in
document 'A6V10210390'.
See also
2
Configuring the extinguishing card [
2